Installation of Solar Collectors
Britain and Ireland pose a greater challenge to the safe installation of panels to
roofs and other supporting structures than is faced in most of Central Europe.. Our western coasts
in particular are much more exposed to storms with strong winds rolling in of the Atlantic.
Collectors fastened to roofs must remain structurally sound over a timescale of at least the
collector design lifetime, which many manufacturers consider to be 30 years. Building Regulations
Section D requires an Agrement Cert, which in turn looks for a 60 year design lifetime
for any components integrated into the roof. In addition to the penetrations of the roof to
fasten the collectors, the installation also requires the collector pipework to be returned
through the roof in a manner that must not compromise the weathertightness of the roof. As
house construction techniques are changing, in the future there may be more 'warm-roofs'
encountered with the insulation installed on top of the rafters, there will be far more interest
in maintaining the structure's airtightness.
Wind loading of collectors
The assessment of wind loadings is a complex process, involving not just a knowledge of
windspeeds and airflow but also of the type and strength of collector, fastenings and
mounting rails and roof structure. The collectors on the roof are subject to force that
create uplift or down lift at right angles to the roof as well as forces along the roof.
(Diagram?) Although some work has been done in this area to develop some national standards
by TNO and BRE, there are no European wide standards at present.
The EU ActiveRoofer project is currently trying to extend the BRE and TNO standards into
a prototype . BRE Digest 489 gives details of the calculations required for solar
PV panels, which could be modified for solar thermal flat-plates and may yield an
approximation of lmiting values for tube-based collectors.
At an installer level, manufacturers advice should be sought on the
suitability of the collectors and mounting systems for the exposure of the site.
as can be seen from the maps below, the assessment of maximum windspeed does depend
on the timescale chosen. A once in fifty year value by the Met Eireann assessment
is almost twice that assumed by BRE for Ireland. Once in fifty years
is within the design lifetime of the roof and is probably a more
representative value to use in assessments.
 |
 |
General Guidance on minimising collector loads
The windspeeds in the maps above are measured at sea level and will increase further with altitude
or due to the concentrating effect of other geographical features that will channel wind.
A site assessment must take these additional factors into account.
Windspeed will also increase on taller buildings or due to the presence of other tall
buildings (that may shield the building from wind from certain directions, but increase
the wind speed from other directions).
Trees, hedges often provide a softer shielding effect and tend to reduce windspeeds over a
horizontal distance of up to ten times their height on the lee side.
Collectors in general should not be positioned topwards the ridge or towards the eaves of the
roof, where vortices can form and increase the uplift forces on the collectors.
The collectors at the edge of a bank of collectors will experience the largest forces.
In exposed locations, it is advisable to increase the number of fixings (reducing their
separation) and also by doubling-up the fixings at each end.
- Keep Collectors (particularily Flat Plate) ½ meter away from the ridge and eves.
- Keep Collectors as low to the roof as possible, to impede wind blowing underneath.
- Provide 200kg of fixing strenght per meter² of panel.
- Double up outside panels fixings if deemed appropiate.
- Flat roof installations, must be especially carefully assessed. One manufacturer recommends 3 x 1,500 kg concrete
sleepers for a 10 meter² panel.
- Vacuum Tube Collectors without reflectors will generally have a much lower wind load, because of the round
profile of the tubes. The gaps between the tubes will help prevent suction forces on the panel.
- Use certified Roof fixing products.
Structural Strength of the Roof
An assessment should be made during the site survey of the nature of the roof to assess
its structural strength. The weight of the collectors is less of a concern for in-roof
systems as the weight per metre squared of the collectors are generally of the same
order as the roof covering they are replacing. For on-roof systems and systems on
flat roofs, the static loading on the roof will increase and this will increase
much more when potential wind loadiing is taken into account. Conventional roof
tend either to be rafter and purlin or truss constructions. Rafter and pulin
constructions tend to use heavier timbers and to have been designed more
conservatively with regard to additional roof loads. Modern truss constructions
are computer designed to minimise the number of trusses and the size of the timbers
required. They tend to have less capacity to take an additional load and more care
should be exercised when assessing loading. Roofs that have special constructions e.g.
hip and valley or that have rafters already cut for rooflight windows should be treated
with even greater care and the location of the collectors kept away from potentially weaker areas.
Tiles, Slates and Sarking
In the UK and Ireland the weatherproof layer of the roof consists of a sarking layer
of felt or membrane over the rafters (trusses), held in place with battens that are
used to support the tiles or slates and allow fixings to be fastened. Concrete
pantiles are generally single lapped and are often only fastened at the ridges,
gables and eaves and around any roof opening. they permit easy installation of
roof hooks since they can be pushed up underneath the tile above or with care
removed for modification. A series of pushed-up tiles are used as means of moving
around the roof by roofers as long as care is taken not to damage the underlying sarking.
Double lapped slates provide a more difficult installation, since they are all
fastened in place and form a more fragile roof covering that may break when walked
upon, particularly in the case of natural slate that has weathered on an older roof.
In assessing roofs, guidelines should be adopted as to when the roof work is beyond
the competence of the installer and is best left to roofing professionals.
On-roof Solar mounting systems
Roofhooks are most easily used on roofs where the tiles can be slid up underneath
one another to expose the sarking and the rafters. Roofhooks are best constructed
from stainless steel. The roofhooks available from continental suppliers often
have a wide spacing of the fixing holes, since rafters there are commonly between
two or three inches wide. Rafters of this width can easily take two staggered
coachbolt fasteners without splitting. The narrower roof timbers found in Ireland
and the UK would be easily damaged by fastening in this way or by the use of
benchscrews of thicker diameter. Roofhooks may have to be modified by drilling
an additional hole and perhaps more of them used to distribute the load over more
trusses, as well as using finer fixings.
Solar Bolts provide an alternative to roofhooks particularly for double-lapped tiles.
To use these the the roof covering is drilled from outside, through the tile or slate
and sarking into the centre of the rafter or a noggin. The alignment of the hole is
critical if drilling into a rafter as it is possible to split the rafter, if the
hole is too close to the edge.
Various techniques can be used to identify the
right point to drill. These include the placing of a rare-earth magnet on the
inside of the rof on the centre of the upper of the rafter and then using a second
magnet outside on the roof to accurately line-up with this. Alternative some
installers drill a small pilot hole from the inside of the roof outwards using
the rafter inside as a guide to ensuring it is centred and then drilling the
full-sized hole from the outside in. Neither of these techniques are advocated
if the rafters are narrow. There is too much risk of causing structural damage
to the roof by splitting the rafters. It is best practice here to fit noggins
between the rafters of at least 50mm thickness, using either joist hangers or
skew-driven screw nails to attach them to the rafters. This can simplify the
benchscrew alignment as the outer hole in the roof can be drilled before the
noggin is fixed and the noggin then aligned to the outer hole (a two-man operation).
The screw is attached at the highest point in the tile profile, so that rain will have a
natural tendency to flow away from the seal. Do not mount the screw in the tile "valley"
as this will block rain water flowing down the roof.
|
A 8.0 mm hole is drilled through the roof tile, normally with a diamond drill bit.
Because the highest point in the tile
profile will only occasionally match up with a rafter below, a noggin can be attached
securely between adjacent rafters in the attic to provide a strong anchor point for the screw.
We recommend (& SEI insist) that the solar bolt is screwed into the wood/rafter a depth of
at least 2 inches or 50mm. A batton with a typical depth of 25mm is therefore not suitable
as a fixing point.
|
 |
In-roof Solar mounting systems
At present only flat-plate collectors can be integrated into the roof in this way.
The collector essentially becomes part of the weatherproof layer of the roof. This
requires a high standard of materials and workmanship to provide durability comparable
to standard roofing such as tiles and slates. Usually collectors will only be
installed in this fashion on a new-build site, as the degree of disturbance to
an existing roof and the cost of the extra labour is not justifiable in a retro-fit
application. On a new build roof, the collector will be installed on top of the
tile battens and then flashed in situ in a similar manner to a roof light.
Generally a header flashing will divert the flow of water coming down the roof
over the top of the collector or around it onto the side flashings. The bottom
edge is finished with a flashing to redirect the flow of the water onto the slates
or tiles underneath. All hydraulic connections are concealed behind the flashing
and this gives the collector a clean appearance on the roof. In addition to
minimising the wind load on the collector, this method of mounting also reduces
the cooling of the rear of the collector and yields a slight increase in efficiency.
Flat Roof Solar mounting systems
Flat roof mounting systems can comprise either aluminium frame systems or plastic containers.
The frames may be either ballasted onto the roof or mechanically fixed to the roof without
breaching the weathertightness. The plastic containers are ballasted only. Ballast
systems will greatly increase the static load on the roof and requires careful
professional assessment of the strength of the roof. Wind loading also requires
professional assessment of the exposure of the site, of the angle, orientation and
size of the collectors and of the holding power of the ballast or mechanical fixings.
Most larger solar companies will be able to provide the required technical advice.
|